Modbus Gateway
The Modbus Gateway is designed for localized, industrial, or commercial installations where water meters are connected via wired communication buses (RS-485).
It serves as a protocol converter, translating the Modbus RTU/ASCII data into Modbus TCP or MQTT format for cloud integration.
Key Features (Modbus Gateway)
- Legacy Integration: Directly interfaces with existing and new water meters supporting the industry-standard Modbus protocol, typically over RS-485.
- Robust & Reliable: Wired connections offer high reliability, faster data transfer, and are less susceptible to radio interference.
- Protocol Conversion: Translates Modbus RTU/ASCII (serial) into Modbus TCP or cloud protocols (MQTT) over Ethernet or Cellular.
- Local Density: Ideal for utility rooms, apartment complexes, or industrial facilities where meters are centrally located and can be wired together.
Technical Specifications (Modbus Gateway)
| Parameter | Specification | Notes |
|---|---|---|
| Meter Protocol (Inbound) | Modbus RTU / ASCII | Communicates with water meters as a Modbus Master. |
| Physical Interface | RS-485 Serial Port(s) | Connects directly to the wired bus of the water meters. |
| Max Devices Supported | 32 slave devices per RS-485 bus segment | Limited by the Modbus protocol and cable length. |
| Max Distance (Approx.) | Up to 1,200 meters (RS-485) | The range is wired and depends on cable quality and baud rate. |
| Backhaul (Outbound) | Cellular | Used to connect to the local network or internet. |
| Baud Rate | 9600 bps (Typical), User Configurable | Standard industrial communication speed. |
| Data Format | 8 Data bits, No Parity, 1 Stop bit (8N1) | User configurable; common Modbus setting. |
| Power Input | 9–32 V DC | Standard industrial power supply range. |
Single-Channel Modbus Gateway
Designed for small-scale installations, connecting water meters over a single RS-485 bus.
-
Key Features:
- Directly interfaces with Modbus RTU/ASCII devices.
- Robust and reliable wired communication.
- Converts data to Modbus TCP or MQTT for cloud integration.
-
Technical Specifications:
| Parameter | Specification |
|---|---|
| RS-485 Channels | 1 |
| Max Devices Supported | 32 slave devices |
| Backhaul (Outbound) | Cellular |
| Baud Rate | 9600 bps (typical), user configurable |
| Power Input | 9–32 V DC |
| Enclosure | IP20 / Industrial-rated |
4-Channel Modbus Gateway
Designed for medium-to-large installations where multiple RS-485 buses are needed.
- Key Features:
- Supports four independent RS-485 channels.
- Each channel can connect multiple devices, increasing total capacity.
- Technical Specifications:
| Parameter | Specification |
|---|---|
| RS-485 Channels | 4 |
| Max Devices Supported | 128 slave devices (4 × 32 per channel) |
| Backhaul (Outbound) | Cellular |
| Baud Rate | 9600 bps (typical), user configurable |
| Power Input | 9–32 V DC |
| Enclosure | IP20 / Industrial-rated |