| Nominal Diameter (DN) | 80 mm |
| Meter Type | Ultrasonic |
| Measuring Principle | Transit-time difference of ultrasonic signals |
| Accuracy Class | Class 2 |
| Nominal Flow Rate (Q₃) | 63 m³/h |
| Overload Flow Rate (Q₄) | 78.75 m³/h |
| Transitional Flow Rate (Q₂) | 2.52 m³/h |
| Minimum Flow Rate (Q₁) | 1.575 m³/h |
| R Ratio (Q₃/Q₁) | R40 |
| Maximum Permissible Error (MPE) | ±2% (Q₂ ≤ Q ≤ Q₄), ±5% (Q₁ ≤ Q < Q₂) |
| Pressure Class | MAP16 |
| Maximum Operating Pressure | 1.6 MPa (16 bar) |
| Pressure Loss Class | ΔP63 |
| Temperature Class | T50 (up to 50°C) |
| Maximum Permissible Temperature | 50°C |
| Nominal Pressure Loss at Q₃ | ≤ 0.063 MPa (63 kPa) |
| Nominal Pipe Connection | Flanged (as per ISO 7005) |
| Mounting Orientation | Horizontal (H) |
| Direction of Flow | Forward (arrow marked on body) |
| Flow Profile Sensitivity | U₀/D₀ = 0 / 0 (not affected by upstream/downstream disturbances) |
| Length of Upstream Straight Pipe | 15D |
| Length of Downstream Straight Pipe | 15D |
| Verification Scale Interval (VSI) | 0.01 Litre |
| Meter Body Material | Cast Iron / Ductile Iron |
| Transducer Housing | Encapsulated Ultrasonic Sensor Pair |
| Display Unit Position | Top of Meter |
| Ingress Protection | IP68 |
| Ambient Temperature Range | 5°C to 55°C |
| Storage Temperature Range | -25°C to +70°C |
| Reference Standards | ISO 4064-1:2014, ISO 4064-3:2014 |
| Typical Application | Bulk water measurement for industrial and municipal usage |